Overview
The Vessel Incidental Discharge Act (VIDA), passed by Congress in 2018, amended Section 312 of the Clean Water Act (CWA) by introducing a new subsection titled “Uniform National Standards for Discharges Incidental to Normal Operation of Vessels.” VIDA aims to streamline the regulatory framework by consolidating federal, state and local requirements for discharges from commercial vessels.
On October 9, 2024, the United States (U.S.) Environmental Protection Agency (EPA) published its final rule under the VIDA, titled “Vessel Incidental Discharge National Standards of Performance” (VID-NSP), establishing federal standards of performance for marine pollution control devices applicable to discharges into U.S. waters and the contiguous zone. The VIDA does not apply to incidental discharges originating from:
- Vessels of the armed forces
- Recreational vessels
- Floating crafts permanently moored to a pier
- Small vessels (less than 79 feet in length) or fishing vessels except for discharges of ballast water.
Harvey Energy Tri-Fuel Vessel Shapes Future of Sustainability
The Harvey Energy will become the first ABS-classed dual fuel and battery vessel and the first U.S. flagged OSV equipped with a battery/converter system.
The U.S. Coast Guard (USCG) is required to develop corresponding implementation, compliance and enforcement regulations within two years of the EPA standards’ publication. These regulations may include requirements related to the design, construction, testing, approval, installation and use of devices necessary to meet the EPA standards.
The effective date of the EPA’s rule is November 8, 2024; however, the federal standards will only become effective once the USCG’s implementing regulations are final, effective, and enforceable. Until then, existing requirements from the 2013 Vessel General Permit (VGP) and the USCG’s requirements under section 1101 of the Nonindigenous Aquatic Nuisance Prevention and Control Act of 1990 (NANPCA) including the regulations in 46 CFR 162.060 and 33 CFR part 151 subparts C and D (as in effect on December 3, 2018), will remain in effect. Once the USCG’s new regulations are final, effective, and enforceable, the requirements of the VGP and related regulations will be repealed.
Discharge Standards of Performance
Two different types of discharge standards of performance have been established under VIDA:
- Discharges Incidental to the Normal Operation of a Vessel — General Standards
- Discharges Incidental to the Normal Operation of a Vessel — Specific Standards
A summary of the requirements applicable to each discharge standard of performance is provided next, along with the corresponding Code of Federal Regulations (CFR) rule site where the full details of each requirement can be found.
General Standards for Discharges Incidental to the Normal Operation of a Vessel
The general discharge standards of performance are organized into three categories: (1) General Operation and Maintenance, (2) Biofouling Management and (3) Oil Management.
1. General Operation and Maintenance (40 CFR 139.4)
The general requirements in this section apply to any discharge incidental to the normal operation of a vessel, including the specific discharges incidental listed in item (B) below.
Vessels must implement practices to minimize discharges, such as proper storage and transfer of materials, and ensure discharges occur when the vessel is underway and far from shore. Adding materials to discharges, except for treatment, or diluting discharges to meet standards is prohibited.
Onboard materials should be used according to manufacturer specifications and comply with U.S. regulations. Cargo must be containerized or covered, except when covering would compromise safety or operations. Toxic or hazardous materials must be stored in sealed, labeled containers located in areas that minimize exposure to ocean spray and precipitation. Such containers should not be overfilled, and incompatible materials must not be mixed. Discharging or disposing of these containers is prohibited.
Before washing compartments or tanks, they must be broom clean. Topside surfaces should be maintained to minimize discharges of cleaning compounds and other similar materials. Painting and coating techniques should minimize discharge, and unused paint and coatings must not be discharged. Equipment must be maintained to prevent leaks or spills of oil, fuel, or other hazardous materials
2. Biofouling Management (40 CFR 139.5)
A biofouling management plan must be developed to minimize the discharge of biofouling organisms prioritizing procedures and strategies to prevent macrofouling and minimizing the potential for the introduction and spread of aquatic nuisance species (ANS). The plan must describe the vessel-specific anti-fouling systems and biofouling management practices.
3. Oil Management (40 CFR 139.6)
The discharge of used or spent oil is prohibited. Control and response measures must be used during fueling, maintenance and other vessel operations to prevent, minimize and contain spills and overflows.
An environmentally acceptable lubricant (EAL) must be used in any oil-to-sea interface unless such use is technically infeasible. Operators of new build vessels should endeavor to use seawater-based systems for stern tube lubrication to eliminate the discharge of oil from these interfaces to the aquatic environment.
Standards for Specific Discharges Incidental to the Normal Operation of a Vessel
The specific discharge standards of performance establish requirements for discharges of 20 different equipment and systems. The requirements are at least as stringent as the VGP. EPA is promulgating changes to the VGP requirements to transition the permit requirements into regulations that reflect national technology-based performance standards, improve clarity, enhance enforceability and implementation, and incorporate new information and technology.
Similarities and Differences Between VID-NSP and VGP
The similarities and differences between the final discharge standards of performance and the VGP can be separated into three groups:
Group |
Comment |
Discharge |
First Group |
Consists of 13 discharge standards that are substantially the same as the requirements of the VGP. These discharge standards encompass the intent and stringency of the VGP but include other changes to conform to the requirements of the VIDA. |
- Boilers
- Cathodic protection
- Chain lockers
- Decks
- Elevator pits
- Fire protection equipment
- Gas turbines
- Inert gas systems
- Motor gasoline and compensating systems
- Non-oily machinery
- Pools and spas
- Refrigeration and air conditioning
- Sonar domes
|
Second Group |
Consists of two consistent discharge standards but slightly modified from the VGP to moderately increase stringency or provide language clarifications. |
- Bilges
- Desalination and purification systems
|
Third Group |
Consists of five discharge standards containing the most significant modifications from the VGP. These modifications address specific VIDA requirements and reflect new information that has become available since the issuance of the VGP.
|
- Ballast tanks
- Exhaust gas emission control systems
- Graywater systems
- Hulls and associated niche areas
- Seawater piping
|
The VID-NSP mandate the implementation of Ballast Water Best Management Practices for vessels equipped with ballast tanks (paragraph 40 CFR 139.10(c)). These vessels must maintain a ballast water management plan that addresses the uptake and discharge of ballast water, including vessel-specific systems and practices. They should minimize gravity drainage of ballast tanks while in port and use high sea suction methods when in port or shallow waters. Furthermore, vessels must avoid discharging or taking on ballast water in areas with coral reefs, ensuring such activities occur as far from coral reefs as practicable. Periodical cleaning of ballast tanks to remove sediment is required, with the discharge of sediment being prohibited. Sea chest screens must be maintained and kept intact. New laker vessels[1] equipped with ballast tanks must install, operate and maintain a ballast water management system (BWMS) that has been type-approved by the USCG.
The VID-NSP adopt the same numeric discharge standards for ballast water as established by VGP, including biological and biocide parameters (paragraph 40 CFR 139.10(d)). Discharges from a BWMS must not exceed the instantaneous maximum limits specified for various-sized living organisms, Toxicogenic Vibrio cholerae, Escherichia coli, intestinal enterococci, and four biocides: chlorine dioxide, total residual oxidizers, peracetic acid and hydrogen peroxide. Both MPN/mL and cfu/mL units are now specified for Escherichia coli and intestinal enterococcito to reflect the MPN outputs of newer microbiological test methods. Exemptions to these ballast water discharge standards apply to certain vessels, such as those less than or equal to 3,000 GT, that do not operate outside the Exclusive Economic Zone (EEZ).
The VID-NSP provide the following ballast water exchange and saltwater flush requirements (paragraph 40 CFR 139.10(e)):
- Any vessel that takes on ballast water in areas less than 200 nautical miles (NM) from shore that will later operate outside the EEZ and more than 200 NM from shore must conduct a ballast water exchange at least 200 NM from any shore before discharging that water. This exchange should be commenced not less than 200 NM from any shore and as early as practicable during the voyage.
- Ballast tanks that are empty or contain unpumpable residual water must be sealed, or ballast water exchange or saltwater flush must be conducted not less than 200 NM from any shore for a voyage originating outside the U.S. or Canadian EEZ; or not less than 50 NM from any shore for a voyage originating within the U.S. or Canadian EEZ.
- Certain vessels, such as those operating exclusively within the internal waters of the U.S. and Canada, are exempt.
Special requirements for ballast water exchange and saltwater flush apply to vessels entering the Great Lakes and those operating in the Pacific Region, with full details available in paragraphs 40 CFR 139.10(f) and 139.10(g).
All the above requirements apply to any vessel equipped with one or more ballast tanks, with certain exclusions. For example, vessels that carry permanent ballast water in sealed tanks that are not subject to discharge and vessels that discharge ballast water only to a reception facility are excluded from these requirements (paragraph 40 CFR 139.10(b)).
[1] New Laker means a vessel 3,000 GT and above, and that operates exclusively in the Great Lakes and the St. Lawrence River west of a rhumb line drawn from Cap des Rosiers to Pointe-de-l'Ouest (West Point), Anticosti Island, and west of a line along 63° W longitude from Anticosti Island to the north shore of the St. Lawrence River, and constructed after the effective date of USCG regulations promulgated pursuant to CWA section 312(p)(5)(A)(i). (40 CFR 139.2)
The requirements of this section apply to discharges of wastewater from the bilge consisting of water and residue that accumulates in a lower compartment of the vessel's hull below the waterline, including any water and residue from a cargo area that comes into contact with oily materials or a below-deck parking area or other storage area for motor vehicles or other motorized equipment.
The discharge of bilgewater from any vessel must not contain flocculants or other additives except when used with an oily water separator or to maintain or clean equipment. Using additives to remove the appearance of a visible sheen is prohibited. For vessels of 400 GT and above, bilgewater discharge must occur when the vessel is underway, at least one NM from shore (if technologically feasible), and have an oil content of 15 ppm or less.
The discharge from boiler blowdown must be minimized in port.
The requirements of this section apply to discharges resulting from a vessel's cathodic corrosion control protection device, including sacrificial anodes and impressed current cathodic protection (ICCP) systems.
The spaces between any flush-fit anode and backing must be filled to remove potential hotspots for biofouling organisms. The vessel operator must consider using, but is not required to use, less toxic metals when selecting sacrificial anodes. It is recommended that vessels operating in harbors or estuaries with high pollutant loads use zinc as the preferred anode material due to concerns with pollutants causing aluminum anodes to passivate and lose effectiveness.
The requirements of this section apply to discharges resulting from a vessel's cathodic corrosion control protection device, including sacrificial anodes and impressed current cathodic protection (ICCP) systems.
The spaces between any flush-fit anode and backing must be filled to remove potential hotspots for biofouling organisms. The vessel operator must consider using, but is not required to use, less toxic metals when selecting sacrificial anodes. It is recommended that vessels operating in harbors or estuaries with high pollutant loads use zinc as the preferred anode material due to concerns with pollutants causing aluminum anodes to passivate and lose effectiveness.
Anchors and anchor chains must be rinsed of biofouling organisms and sediment when the anchor is retrieved. Discharging biological organisms, sediment, precipitation and seawater from any chain locker is prohibited in port.
Anchors and anchor chains used beyond the waters of the contiguous zone must be rinsed of biofouling organisms and sediment prior to entering the contiguous zone. This requirement may be met by rinsing when the anchor is retrieved at the commencement of the voyage or when the anchor was last retrieved on a previous voyage, so long as the rinsing occurs after the last use of the anchor beyond the waters of the contiguous zone.
This section applies to the discharge of washdown and runoff from decks, well decks, and bulkhead areas, including precipitation, condensation, seawater spray and wash over, and flooding, as well as waters pumped from below deck on a barge.
Coaming or drip pans must be used for machinery that is expected to leak or otherwise release oil on the deck; accumulated oil must be collected. Where required by an applicable treaty or convention or the USCG, the vessel must be fitted with and use physical barriers, such as spill rails and scuppers, during washdowns.
Control measures must be used to minimize the introduction of on-deck debris, garbage and other materials into deck washdown and runoff (paragraph 40 CFR 139.15(d)). Decks must be kept in broom clean condition whenever the vessel is underway and before washdowns. Any soap, cleaner, or detergent used must be minimally toxic, phosphate-free and biodegradable.
Discharges from deck washdowns should be minimized while in port. Barges that discharge water pumped from below deck must minimize the contact of below-deck condensation with oily or toxic materials and any materials containing hydrocarbons.
The discharge resulting from the cleaning of desalination and purification systems with toxic or hazardous materials is prohibited.
The discharge of untreated accumulated water and sediment from any elevator pit is prohibited.
The VID-NSP establish limits for the following parameters in the discharges from the operation and cleaning of any exhaust gas cleaning system (EGCS) and exhaust gas recirculation (EGR) system: pH, PAHs (Polycyclic Aromatic Hydrocarbons), turbidity, suspended particulate matter and nitrates plus nitrites. The same limits apply for pH, PAH and turbidity for any EGCS water retained in a temporary storage tank prior to discharge.
The discharges of sludge or residues generated from the treatment of EGCS or EGR washwater or bleed-off water are prohibited.
For a vessel operating on fuel that meets the sulfur content limits specified in Regulation 14 of MARPOL Annex VI, discharge of EGR bleed-off water is excluded from the requirements above if the vessel does not retain the EGR bleed-off onboard in a holding tank prior to discharge, is underway and not in port.
For a vessel not operating on fuel that meets the sulfur content limits specified in Regulation 14 of MARPOL Annex VI, discharge of EGR bleed-off water retained in a holding tank is prohibited unless the vessel is underway, not in port and in compliance with the discharge standard requirements above.
The table below summarizes the main differences and clarifications between the VID-NSP and VGP regarding the discharge standards for exhaust gas emission control systems. It is important to note that VGP did not address EGR discharges, primarily because EGR systems are relatively new to vessels.
Parameter
|
VGP
|
VID-NSP
|
pH
|
The discharge of washwater from the exhaust gas scrubber treatment system must have a pH of no less than 6.0 measured at the ship’s overboard discharge, with the exception that during maneuvering and transit, the maximum difference between inlet and outlet of 2.0 pH units is allowed. This difference is to be measured at the ship’s inlet and overboard discharge.
|
The discharge must meet one of the following requirements:
- The discharge must have a pH of no less than 6.5 as measured at the vessel's overboard discharge point with the exception that during maneuvering and transit, the maximum difference of 2.0 pH units is allowed between inlet water and overboard discharge values; or
- The pH discharge limit is the value that will achieve a minimum pH of 6.5 at 4 meters from the overboard discharge point with the vessel stationary. This overboard pH discharge limit is to be determined at the overboard discharge monitoring point and is to be recorded as the vessel's discharge limit. The overboard pH limit can be determined either by means of direct measurement, or by using a calculation-based methodology (computational fluid dynamics or other equally scientifically established empirical formulas).
The pH numeric discharge standard may be exceeded for up to 15 minutes in any 12-hour period.
|
PAH
|
The maximum continuous PAH concentration in the washwater must not be greater than 50 μg/L PAHphe (phenanthrene equivalence) above the inlet water PAH concentration for washwater flow rates normalized to 45 t/MWh. MWh refers to the maximum continuous rating (MCR) or 80% of the power rating of the fuel oil combustion unit.
|
The maximum continuous PAH concentration in the discharge must be no greater than 50 µg/L PAHphe (phenanthrene equivalents) above the inlet water PAH concentration. The 50 µg/L numeric discharge standard is normalized for a discharge flow rate, before any seawater neutralization for pH control, of 45 t/MWh where the MW refers to the Maximum Continuous Rating (MCR) or 80% of the power rating of the fuel oil combustion units whose EGCS discharge water PAH is being monitored at that point.
In cases where sensors are installed in a separate measurement cell, the PAH limit applies to the flow in the main discharge pipe from which the water is bypassed.
|
Turbidity
|
For a maximum of one 15-minute period within any 12-hour period, the continuous turbidity discharge limit may be exceeded by 20%.
|
For an aggregated 15-minute period in any rolling 12-hour period, the continuous turbidity discharge limit may be exceeded by 20%.
|
Nitrates plus nitrites
|
MWh refers to the MCR or 80% of the power rating of the fuel oil combustion unit.
|
MW refers to the MCR or 80% of the power rating of all those fuel oil combustion units whose EGCS discharge water nitrates plus nitrites are being monitored at that point.
|
Nitrates plus nitrites
|
- For a discharge water flow rate of 5 t/MWh, the nitrate plus nitrite limit is 640 mg/L.
- For a discharge water flow rate of 90 t/MWh, the nitrate plus nitrite limit is 30 mg/L.
|
- For a discharge water flow rate of 5 t/MWh, the nitrate plus nitrite limit is 540 mg/L.
- For a discharge water flow rate of 90 t/MWh, the nitrate plus nitrite limit has been removed.
|
PAH, turbidity, and nitrates plus nitrites
|
For these criteria, the PAH and nitrates plus nitrites concentrations and the turbidity in the washwater must be measured:
Downstream of the water treatment equipment; but
Upstream of washwater dilution (or other reactant dosing) prior to discharge.
|
These standards apply:
Downstream of the water treatment equipment including any reactant dosing unit; but
Upstream of any seawater addition for pH control prior to discharge.
|
The VID-NSP establish requirements for discharges from fire protection equipment, including discharges for secondary purposes, such as anchor and anchor chain rinsing and deck washdown. These requirements do not apply during emergencies or when compliance would compromise the safety of the vessel or life at sea.
The discharge of fluorinated firefighting foam is prohibited unless required for certification or inspection or by the marine inspector to ensure vessel safety and seaworthiness.
The discharge from fire protection equipment during testing, training, maintenance, inspection or certification is prohibited in port unless the intake is from surrounding waters or a potable water supply and contains no additives or, if required, in port for certification or inspection or by the marine inspector for safety purposes. The discharge for secondary uses is prohibited in port unless the intake is from surrounding waters or a potable water supply, contains no additives and the discharge meets applicable requirements for secondary use.
The discharge of untreated gas turbine washwater is prohibited unless it is infeasible to do otherwise.
These requirements apply to graywater discharges, except for those from commercial vessels on the Great Lakes, which are subject to 40 CFR 140 and 33 CFR 159. The introduction of kitchen waste, food, oils and oily residues into the graywater system must be minimized. Soaps, cleaners, detergents and other substances used by vessel operators or provided by vessel operators to persons onboard and discharged in graywater must be minimally toxic, phosphate-free and biodegradable.
Vessels subject to paragraph 40 CFR 139.21(e) must meet the following numeric discharge standards established in paragraph 40 CFR 139.21(f):
1. Fecal coliform
|
- The 30-day geometric mean must not exceed 20 colony-forming units (cfu), or Most Probable Number (MPN), per 100 mL.
- Greater than 90% of samples must not exceed 40 cfu, or MPN, per 100 mL during any 30-day period.
|
2. BOD5
|
- The 30-day average must not exceed 30 mg/L.
- The 7-day average must not exceed 45 mg/L.
|
3. Suspended solids
|
- The 30-day average must not exceed 30 mg/L.
- The 7-day average must not exceed 45 mg/L.
|
4. pH
|
It must be maintained between 6.0 and 9.0.
|
5. Total residual oxidizers
|
For any discharge from a graywater system using chlorine, total residual oxidizers must not exceed 10.0 µg/L.
|
The table below summarizes the main differences and clarifications between the VID-NSP and VGP regarding the discharge standards for graywater systems.
Parameter
|
VGP
|
VID-NSP
|
Fecal coliform
|
The geometric mean of the samples from the discharge during any 30-day period may not exceed 20 fecal coliform/100 mL and not more than 10% of the samples may exceed 40 fecal coliform/100 mL.
|
a. The 30-day geometric mean must not exceed 20 colony-forming units (cfu), or MPN, per 100 mL.
b. Greater than 90% of samples must not exceed 40 cfu, or MPN, per 100 mL during any 30-day period.
|
BOD5
|
a. The 30-day average shall not exceed 30 mg/L.
b. The 7-day average shall not exceed 45 mg/L.
c. The 30-day average percent removal shall not be less than 85%.
d. At the option of the National Pollutant Discharge Elimination System (NPDES) permitting authority, in lieu of the parameter BOD5 and the specified levels of the effluent quality, the parameter CBOD5 may be substituted with the following levels of the CBOD5 effluent quality provided:
1. The 30-day average shall not exceed 25 mg/L.
2. The 7-day average shall not exceed 40 mg/L.
3. The 30-day average percent removal shall not be less than 85%.
|
a. The 30-day average must not exceed 30 mg/L.
b. The 7-day average must not exceed 45 mg/L.
|
Suspended solids
|
a. The 30-day average shall not exceed 30 mg/L.
b. The 7-day average shall not exceed 45 mg/L.
c. The 30-day average percent removal shall not be less than 85%.
|
a. The 30-day average must not exceed 30 mg/L.
b. The 7-day average must not exceed 45 mg/L.
|
pH
|
The effluent values for pH shall be maintained within the limits of 6.0 to 9.0 unless the publicly owned treatment works demonstrate that:
a. Inorganic chemicals are not added to the waste stream as part of the treatment process; and
b. contributions from industrial sources do not cause the pH of the effluent to be less than 6.0 or greater than 9.0.
|
Must be maintained between 6.0 and 9.0.
|
Total residual oxidizers
|
Concentrations of total residual chlorine may not exceed 10.0 µg/L.
|
For any discharge from a graywater system using chlorine, total residual oxidizers must not exceed 10.0 µg/L.
|
Graywater discharge is prohibited from any vessel:
- Within 3 NM from shore that voyages at least 3 NM from shore and has remaining available graywater storage capacity, unless the discharge meets the specified numeric standards; and
- Within 1 NM from shore that voyages at least 1 NM from shore but not beyond 3 NM from shore and has remaining available graywater storage capacity, unless the discharge meets the specified numeric standards.
Except for vessels subject to paragraph 40 CFR 139.21(e), graywater discharge from non-commercial vessels operating on the Great Lakes must not exceed 200 fecal cfu per 100 mL and contain no more than 150 mg/L of suspended solids.
These requirements apply to the discharge of anti-fouling coatings, biofouling organisms, and other materials from vessel hulls and associated niche areas. The transport of attached living organisms and passive discharge of biofouling must be minimized when vessels enter U.S. waters from outside the EEZ or travel between Captain of the Port (COTP) Zones.
Anti-fouling coatings applied to vessels must be specific to the vessels’ operational profile and equipment, and biocidal coatings should have appropriate biocide release rates and components that are biodegradable once separated from the vessel surface. Anti-fouling coatings must be applied, maintained and reapplied according to manufacturer specifications, including thickness, method of application, and lifespan of the coating. Furthermore, they must not contain cybutryne, tributyltin (TBT) or any other organotin compound used as a biocide. Additional requirements for anti-fouling coatings are provided in paragraph 40 CFR 139.22(c).
Cleaning should be conducted in drydock when practicable, and hulls must be managed to minimize biofouling. Cleaning must minimize damage to anti-fouling coatings, minimize biocide release and adhere to the requirements found on the coating manufacturers’ instructions and any applicable FIFRA label. Discharges from in-water cleaning without capturing macrofouling or copper-based coatings in copper-impaired waters within the first 365 days after application are prohibited. In-water cleaning must not be conducted on any section of an anti-fouling coating that shows excessive cleaning actions or blistering due to the internal failure of the paint system. Any soap, cleaner, or detergent used must be minimally toxic, phosphate-free and biodegradable (paragraph 40 CFR 139.22(d)).
There are no additional discharge-specific requirements that apply to the discharge of washwater from an inert gas system and deck seal water when used as an integral part of that system.
The discharge of motor gasoline and compensating discharges in federally protected waters is prohibited.
These requirements apply to discharges from machinery containing no oil as detailed in paragraph 40 CFR 139.25(a). It is prohibited to discharge untreated non-oily machinery wastewater and packing gland or stuffing box effluent with toxic or bioaccumulative additives or oil in harmful quantities.
Except for unintentional releases from overflows across the decks and into overboard drains caused by weather, vessel traffic or other navigational factors, the discharge of pool and spa water must occur only while the vessel is underway unless deemed unfeasible. Such discharges must meet the following numeric standards, which are the same as those established by VGP:
- For chlorine disinfection: total residual chlorine must be less than 100 µg/L.
- For bromine disinfection: total residual oxidant must be less than 25 µg/L.
The requirements for discharges from refrigeration, air conditioning and similar chilling equipment specify that the direct overboard discharge of condensate that contacts toxic or hazardous materials is prohibited.
The requirements for discharges from seawater piping systems apply in port and during layup. Seawater piping systems must be inspected, maintained and cleaned as necessary to minimize the accumulation and discharge of biofouling organisms. Seawater piping systems that accumulate macrofouling must be fitted with a Marine Growth Prevention System (MGPS) addressing the level, frequency, and type of expected biofouling, as well as the design, location, and area in which the system will be used. An MGPS must include one or a combination of the following methods: chemical injection, electrolysis, ultrasound, ultraviolet radiation, electrochlorination, antifouling coatings, cupro-nickel piping, or glass-reinforced epoxy-based composite piping. Upon identification of macrofouling, reactive measures must be implemented; however, discharges resulting from these measures are prohibited while in port.
The discharge of water from inside the sonar dome is prohibited during maintenance or repair. Any discharge from the use of bioaccumulative biocides on the exterior of the sonar dome is also prohibited when non-bioaccumulative alternatives are available.
Special Area Requirements — Vessels Operating in Federally Protected Waters
The requirements of this section are in addition to each general or specific discharge standard when the vessel is operating in federally protected waters:
- Ballast Tanks: The discharge or uptake of ballast water in federally protected waters must be avoided, with certain exceptions in paragraph 40 CFR 139.40(b).
- Bilge: For any vessel of 400 GT and above, the discharge of bilgewater into federally protected waters is prohibited.
- Boilers: The discharge of boiler blowdown into federally protected waters is prohibited.
- Chain Lockers: The discharge of accumulated water and sediment from any chain locker into federally protected waters is prohibited.
- Decks: The discharge of deck washdown into federally protected waters is prohibited except for those vessels operating exclusively within these protected waters, provided the discharge complies with all other requirements in section 40 CFR 139.15.
- Fire Protection Equipment: The discharge from fire protection equipment into federally protected waters is prohibited except to comply with USCG fire drill requirements or anchor and anchor chain requirements in section 40 CFR 139.14. When USCG fire drills are conducted, the discharge of any firefighting foam into federally protected waters is prohibited except by any vessel owned or under contract with the U.S., State or local government to do business exclusively in any federally protected waters.
- Graywater Systems: The discharge of graywater into federally protected waters from any vessel with remaining available graywater storage capacity is prohibited.
- Hulls and Associated Niche Areas: The discharge from in-water cleaning of vessel hulls and niche areas into federally protected waters is prohibited except by any vessel owned or under contract with the U.S., State or local government to do business exclusively in any federally protected waters.
- Motor Gasoline and Compensating Systems: The discharge of motor gasoline and compensating discharges into federally protected waters is prohibited.
- Pools and Spas: The discharge of pool or spa water into federally protected waters is prohibited.
- Seawater Piping Systems: The discharge of chemical dosing, as described in section 40 CFR 139.28, into federally protected waters is prohibited.
The list of all federally protected waters can be found in Appendix A to Part 139.